nybjtp

products

PXXHDC 56-2 Porcelain Pin Insulator

short description:

Diameter (D): 9 Inches (229mm)

Spacing (H): 6 1/2Inches (165mm)

Leakage Distance: 17Inches (432mm)

Minimum Pin Height: 7Inches (178mm)

Net Weight Each: 11 6/9 Pounds (5.3kg)


Product Detail

Product Tags

Description

Place of origin: China
Brand name: PXXHDC
Model name: 56-2
Type: insulator
Material: porcelain
Application: low voltage
Tensile strength:13.2kN
Color: white and brown
Product name: 56-2 pin insulator
Certification: ISO9001/ISO14001/ISO18001
Usage: Insulation protection
Standard: ANSI/IEC60383
Advantage: factory price, high quality
Packing: carton box
MOQ: 1000 Pieces

Mechanical Values

Cantilever Strength: 3,000Pounds (13.2kN)

Electrical Values

Typical Application Voltage: 22kV
Low-frequency Dry Flashover Voltage: 110kV
Low-frequency Wet Flashover Voltage: 70kV
Critical Impulse Flashover Voltage, Positive: 175kV
Critical Impulse Flashover Voltage, Negative: 225kV
Low-frequency Puncture Voltage: 145kV
RIV Test Voltage to Ground: 10kV
Maximum RIV at 1,000kHz: 50μV

Insulator classes

Overhead line string insulators are divided into two classes according to their design.
Class A: an insulator or insulator unit in which the length of the shortest puncture path through solid insulating material is at least equal to half the arcing distance. An example of a class A insulator is a long rod insulator with external fittings.
Class B:an insulator or insulator unit in which the length of the shortest puncture path through solid insulating material is less than half the arcing distance. An example of a class B insulator is a cap and pin insulator.

Insulator types

For the purposes of the parts of IEC60383. Overhead line insulators are divided into the four following types:
—pin insulators
—line post insulators
—string insulator units, divided into two sub-types:
Cap and pin insulators
Long rod insulators
Insulators for overhead electric traction lines.

Pin insulator

A rigid insulator consisting of an insulating component intended to be mounted rigidly on a supporting structure by means of a pin passing up inside the insulator. The insulating component may consist of one or more pieces of insulating material permanently connected together. The fixing of the insulating component to the pin can either be separable or permanent (pin insulator with integral pin).